WAGO-I/O-SYSTEM 750 I/O Modules 231758-874/000-131 WAGO-I/O-IPC-C6ManualVersion 1.0.018.2.2.4 4 Channel Digital Output Modules750-504, -516, -519, -531,753-504, -516, -531, -540Table 92: 4 Channel Digital Output ModulesOutput Process ImageBit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0controlsDO 4Channel 4controlsDO 3Channel 3controlsDO 2Channel 2controlsDO 1Channel 118.2.2.5 4 Channel Digital Output Modules with Diagnostics and InputProcess Data750-532The digital output modules have a diagnostic bit for each output channel. When anoutput fault condition occurs (i.e., overload, short circuit, or broken wire), adiagnostic bit is set. The diagnostic data is mapped into the Input Process Image,while the output control bits are in the Output Process Image.Table 93: 4 Channel Digital Output Modules with Diagnostics and Input Process DataInput Process ImageBit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0DiagnosticbitS 4Channel 4DiagnosticbitS 3Channel 3DiagnosticbitS 2Channel 2DiagnosticbitS 1Channel 1Diagnostic bit S = ‘0’ no ErrorDiagnostic bit S = ‘1’ overload, short circuit, or broken wireOutput Process ImageBit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0controlsDO 4Channel 4controlsDO 3Channel 3controlsDO 2Channel 2controlsDO 1Channel 118.2.2.6 8 Channel Digital Output Module750-530, -536, -1515, -1516753-530, -534Table 94: 8 Channel Digital Output ModuleOutput Process ImageBit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0controlsDO 8Channel 8controlsDO 7Channel 7controlsDO 6Channel 6controlsDO 5Channel 5controlsDO 4Channel 4controlsDO 3Channel 3controlsDO 2Channel 2controlsDO 1Channel 1