10.2.7 Technical dataTable 175:SMBRREC (79) technical dataFunction Range or value AccuracyNumber of autoreclosing shots 1 - 5 -Autoreclosing open time:shot 1 - t1 3Ph (0.000-60.000) s ± 0.5% ± 25 msshot 2 - t2 3Phshot 3 - t3 3Phshot 4 - t4 3Phshot 5 - t5 3Ph(0.00-6000.00) sAutorecloser maximum wait time for sync (0.00-6000.00) sMaximum trip pulse duration (0.000-60.000) sInhibit reset time (0.000-60.000) sReset time (0.00-6000.00) sMinimum time CB must be closed before ARbecomes ready for autoreclosing cycle(0.00-6000.00) sCB check time before unsuccessful (0.00-6000.00) sWait for master release (0.00-6000.00) sWait time after close command before proceedingto next shot(0.000-60.000) s10.3 Apparatus control10.3.1 FunctionalityThe apparatus control function APC8 for up to 8 apparatuses is used for control andsupervision of circuit breakers, disconnectors and grounding switches within a bay.Permission to operate is given after evaluation of conditions from other functions such asinterlocking, synchronism check, operator place selection and external or internalblockings.In normal security, the command is processed and the resulting position is not supervised.However with enhanced security, the command is processed and the resulting position issupervised.The switch controller SCSWI initializes and supervises all functions to properly select andoperate switching primary apparatuses. Each of the 8 switch controllers SCSWI mayhandle and operate on one three-phase apparatus.Section 10 1MRK 511 287-UUS AControl248Technical manual