Name Type DescriptionUPD_BLKD BOOLEAN Update of position indication is blockedPOSITION INTEGER Apparatus position indicationOPENPOS BOOLEAN Apparatus open positionCLOSEPOS BOOLEAN Apparatus closed positionTR_POS INTEGER Truck position indicationCNT_VAL INTEGER Operation counter valueL_CAUSE INTEGER Latest value of the error indication during command10.3.4.5 SettingsTable 184:SXSWI Non group settings (basic)Name Values (Range) Unit Step Default DescriptiontStartMove 0.000 - 60.000 s 0.001 3.000 Supervision time for the apparatus to moveafter a commandtIntermediate 0.000 - 60.000 s 0.001 15.000 Allowed time for intermediate positionAdaptivePulse Not adaptiveAdaptive- - Not adaptive Output resets when a new correct end positionis reachedtOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open commandtClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close commandSwitchType Load BreakDisconnectorGrounding SwitchHS Groundg.Switch- - Disconnector 1=LoadBreak,2=Disconnector,3=GroundSw,4=HighSpeedGroundSwSuppressMidPos DisabledEnabled- - Enabled Mid-position is suppressed during the timetIntermediate10.3.5 Bay control QCBAY10.3.5.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberBay control QCBAY - -1MRK 511 287-UUS A Section 10Control255Technical manual