12.15.5 SettingsTable 415:SPVNZBAT Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Enabled Disable/Enable OperationRtdBattVolt 20.00 - 250.00 V 1.00 110.00 Battery rated voltageBattVoltLowLim 60 - 140 %Vbat 1 70 Lower limit for the battery terminal voltageBattVoltHiLim 60 - 140 %Vbat 1 120 Upper limit for the battery terminal voltagetDelay 0.000 - 60.000 s 0.001 0.200 Delay time for alarmtReset 0.000 - 60.000 s 0.001 0.000 Time delay for reset of alarm12.15.6 Measured valuesTable 416:SPVNZBAT Measured valuesName Type Default DescriptionV_BATT REAL 0.00 Battery terminal voltage that has to be supervisedBLOCK BOOLEAN 0 Blocks all the output signals of the function12.15.7 Monitored DataTable 417:SPVNZBAT Monitored dataName Type Values (Range) Unit DescriptionBATTVOLT REAL - kV Service value of the batteryterminal voltage12.15.8 Operation principleThe function can be enabled and disabled with the Operation setting. The correspondingparameter values are Enable and Disable.The function execution requires that at least one of the function outputs isconnected in configuration.The operation of the station battery supervision function can be described by using amodule diagram. All the modules in the diagram are explained in the next sections.1MRK 511 287-UUS A Section 12Monitoring517Technical manual