Name Values (Range) Unit Step Default DescriptionIMagComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 5% of InIMagComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 30% ofInIMagComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 100%of InIAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of InIAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of InIAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of In12.1.3.5 Monitored dataTable 346:CMMXU Monitored dataName Type Values (Range) Unit DescriptionI_A REAL - A IA AmplitudeIA_ANGL REAL - deg IA AngleI_B REAL - A IB AmplitudeIB_ANGL REAL - deg IB AngleI_C REAL - A IC AmplitudeIC_ANGL REAL - deg IC Angle12.1.4 Phase-phase voltage measurement VMMXU12.1.4.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberPhase-phase voltage measurement VMMXUUSYMBOL-UU V1 EN-12.1.4.2 Function blockThe available function blocks of an IED are depending on the actual hardware (TRM) andthe logic configuration made in PCM600.Section 12 1MRK 511 287-UUS AMonitoring428Technical manual