Table 269:PULSETIMER Output signalsName Type DescriptionOUT BOOLEAN Output signalSettingsTable 270:PULSETIMER Non group settings (basic)Name Values (Range) Unit Step Default Descriptiont 0.000 - 90000.000 s 0.001 0.010 Pulse time length11.3.1.5 Controllable gate function block GATEIdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberControllable gate function block GATE - -FunctionalityThe GATE function block is used for controlling if a signal should pass from the input tothe output or not, depending on setting.Function blockGATEINPUT OUTIEC09000295-1-en.vsdIEC09000295 V1 ENFigure 170: GATE function blockSignalsTable 271:GATE Input signalsName Type Default DescriptionINPUT BOOLEAN 0 Input signalTable 272:GATE Output signalsName Type DescriptionOUT BOOLEAN Output signal1MRK 511 287-UUS A Section 11Logic377Technical manual