Name Values (Range) Unit Step Default DescriptionThreshold6 6 - 900 %VB 1 65 Threshold in percentage of station batteryvoltage for input 6DebounceTime6 0.000 - 0.100 s 0.001 0.005 Debounce time for input 6OscillationCount6 0 - 255 - 1 0 Oscillation count for input 6OscillationTime6 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 6Threshold7 6 - 900 %VB 1 65 Threshold in percentage of station batteryvoltage for input 7DebounceTime7 0.000 - 0.100 s 0.001 0.005 Debounce time for input 7OscillationCount7 0 - 255 - 1 0 Oscillation count for input 7OscillationTime7 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 7Threshold8 6 - 900 %VB 1 65 Threshold in percentage of station batteryvoltage for input 8DebounceTime8 0.000 - 0.100 s 0.001 0.005 Debounce time for input 8DebounceTime8 0 - 255 - 1 0 Oscillation count for input 8OscillationTime8 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 8Threshold9 6 - 900 %VB 1 65 Threshold in percentage of station batteryvoltage for input 9DebounceTime9 0.000 - 0.100 s 0.001 0.005 Debounce time for input 9OscillationCount9 0 - 255 - 1 0 Oscillation count for input 9OscillationTime9 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 94.1.3.2 Setting parameters for communication moduleTable 10:COM05_12BI Non group settings (basic)Name Values (Range) Unit Step Default DescriptionBatteryVoltage 24 - 250 V 1 110 Station battery voltageTable 11:COM05_12BI Non group settings (advanced)Name Values (Range) Unit Step Default DescriptionThreshold1 6 - 900 %VB 1 65 Threshold in percentage of station batteryvoltage for input 1DebounceTime1 0.000 - 0.100 s 0.001 0.005 Debounce time for input 1OscillationCount1 0 - 255 - 1 0 Oscillation count for input 1OscillationTime1 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 1Threshold2 6 - 900 %VB 1 65 Threshold in percentage of station batteryvoltage for input 2DebounceTime2 0.000 - 0.100 s 0.001 0.005 Debounce time for input 2OscillationCount2 0 - 255 - 1 0 Oscillation count for input 2Table continues on next page1MRK 511 287-UUS A Section 4Binary input and output modules57Technical manual