Table 332:Outputs and their values when activatedName of OUTx Type Description Value whenactivatedValue whendeactivatedOUT1 BOOLEAN Output 1 1 0OUT2 BOOLEAN Output 2 2 0OUT3 BOOLEAN Output 3 4 0OUT4 BOOLEAN Output 4 8 0OUT5 BOOLEAN Output 5 16 0OUT6 BOOLEAN Output 6 32 0OUT7 BOOLEAN Output 7 64 0OUT8 BOOLEAN Output 8 128 0OUT9 BOOLEAN Output 9 256 0OUT10 BOOLEAN Output 10 512 0OUT11 BOOLEAN Output 11 1024 0OUT12 BOOLEAN Output 12 2048 0OUT13 BOOLEAN Output 13 4096 0OUT14 BOOLEAN Output 14 8192 0OUT15 BOOLEAN Output 15 16384 0OUT16 BOOLEAN Output 16 32768 0The sum of the numbers in column “Value when activated” when all OUTx (1≤x≤16) areactive equals 65535. This is the highest integer that can be converted to boolean by theIB16FCVB function block.The operator position input (PSTO) determines the operator place. The integer numberthat is communicated to the IB16FCVB can only be written to the block while the PSTOis in position “Remote”. If PSTO is in position ”Off” or ”Local”, then no changes areapplied to the outputs.11.9 Elapsed time integrator with limit transgression andoverflow supervision TEIGGIO11.9.1 IdentificationFunction Description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2 devicenumberElapsed time integrator TEIGGIO - -1MRK 511 287-UUS A Section 11Logic413Technical manual