Input position (Value) Signal quality Output OPENPOS Output CLOSEPOS0 (Breaker intermediate) Good 0 01 (Breaker open) Good 1 02 (Breaker closed) Good 0 13 (Breaker faulty) Good 0 0Any Invalid 0 0Any Oscillatory 0 010.4.11.5 SignalsTable 225:POS_EVAL Input signalsName Type Default DescriptionPOSITION INTEGER 0 Position status including qualityTable 226:POS_EVAL Output signalsName Type DescriptionOPENPOS BOOLEAN Open positionCLOSEPOS BOOLEAN Close position10.4.11.6 SettingsThe function does not have any settings available in Local HMI or Protection and ControlIED Manager (PCM600).10.4.12 Operation principleThe interlocking function consists of software modules located in each control IED. Thefunction is distributed and not dependent on any central function. Communicationbetween modules in different bays is performed via the station bus.The reservation function is used to ensure that HV apparatuses that might affect theinterlock are blocked during the time gap, which arises between position updates. This canbe done by means of the communication system, reserving all HV apparatuses that mightinfluence the interlocking condition of the intended operation. The reservation ismaintained until the operation is performed.After the selection and reservation of an apparatus, the function has complete data on thestatus of all apparatuses in the switchyard that are affected by the selection. Otheroperators cannot interfere with the reserved apparatus or the status of switching devicesthat may affect it.Section 10 1MRK 511 287-UUS AControl342Technical manual