Name Type DescriptionPF REAL Power factor magnitude of deadband valuePF_RANGE INTEGER Power factor rangeILAG BOOLEAN Current is lagging voltageILEAD BOOLEAN Current is leading voltageU REAL Calculated voltage magnitude of deadband valueU_RANGE INTEGER Calcuated voltage rangeI REAL Calculated current magnitude of deadband valueI_RANGE INTEGER Calculated current rangeF REAL System frequency magnitude of deadband valueF_RANGE INTEGER System frequency range12.1.2.4 SettingsTable 339:CVMMXN Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Disable/Enable OperationGlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base ValuegroupsMode A, B, CAronePos SeqABBCCAABC- - A, B, C Selection of measured current and voltagePowAmpFact 0.000 - 6.000 - 0.001 1.000 Magnitude factor to scale power calculationsPowAngComp -180.0 - 180.0 Deg 0.1 0.0 Angle compensation for phase shift betweenmeasured I & Vk 0.00 - 1.00 - 0.01 0.00 Low pass filter coefficient for powermeasurementSLowLim 0.0 - 2000.0 %SB 0.1 80.0 Low limit in % of SBaseSLowLowLim 0.0 - 2000.0 %SB 0.1 60.0 Low Low limit in % of SBaseSMin 0.0 - 2000.0 %SB 0.1 50.0 Minimum value in % of SBaseSMax 0.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBaseSRepTyp CyclicDead bandInt deadband- - Cyclic Reporting typePMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBaseTable continues on next pageSection 12 1MRK 511 287-UUS AMonitoring422Technical manual