12.22.2 Function blockIEC10000290-1-en.vsdI103EFBLOCK51_EFFW52_EFREVIEC10000290 V1 ENFigure 245: I103EF function block12.22.3 SignalsTable 438:I103EF Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of status reporting51_EFFW BOOLEAN 0 Information number 51, ground-fault forward52_EFREV BOOLEAN 0 Information number 52, ground-fault reverse12.22.4 SettingsTable 439:I103EF Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 160 Function type (1-255)12.23 Function status fault protection for IEC 60870-5-103I103FLTPROT12.23.1 FunctionalityI103FLTPROT is used for fault indications in monitor direction. Each input on thefunction block is specific for a certain fault type and therefore must be connected to acorrespondent signal present in the configuration. For example: 68_TRGEN representsthe General Trip of the device, and therefore must be connected to the general trip signalSMPPTRC_TRIP or equivalent.The delay observed in the protocol is the time difference in between the signal that istriggering the Disturbance Recorder and the respective configured signal to the IEC60870-5-103 I103FLTPROT.Section 12 1MRK 511 287-UUS AMonitoring544Technical manual