Table 189:LOCREM Output signalsName Type DescriptionOFF BOOLEAN Control is disabledLOCAL BOOLEAN Local control is activatedREMOTE BOOLEAN Remote control is activatedVALID BOOLEAN Outputs are valid10.3.6.5 SettingsTable 190:LOCREM Non group settings (basic)Name Values (Range) Unit Step Default DescriptionControlMode Internal LR-switchExternal LR-switch- - Internal LR-switch Control mode for internal/external LR-switch10.3.7 Local remote control LOCREMCTRL10.3.7.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberLocal remote control LOCREMCTRL - -10.3.7.2 FunctionalityThe signals from the local HMI or from an external local/remote switch are applied via thefunction blocks LOCREM and LOCREMCTRL to the Bay control QCBAY functionblock. A parameter in function block LOCREM is set to choose if the switch signals arecoming from the local HMI or from an external hardware switch connected via binaryinputs.Section 10 1MRK 511 287-UUS AControl258Technical manual