10.3.2.5 SettingsTable 178:SCSWI Non group settings (basic)Name Values (Range) Unit Step Default DescriptionCtlModel Dir NormSBO Enh- - SBO Enh Specifies control model typePosDependent Always permittedNot perm at 00/11- - Always permitted Permission to operate depending on thepositiontSelect 0.000 - 60.000 s 0.001 30.000 Maximum time between select and executesignalstSynchrocheck 0.00 - 600.00 s 0.01 10.00 Allowed time for synchronism-check to fulfilclose conditionstSynchronizing 0.00 - 600.00 s 0.01 0.00 Supervision time to get the signalsynchronizing in progresstExecutionFB 0.00 - 600.00 s 0.01 30.00 Maximum time from command execution totermination10.3.3 Circuit breaker SXCBR10.3.3.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberCircuit breaker SXCBR - -10.3.3.2 FunctionalityThe purpose of Circuit breaker (SXCBR) is to provide the actual status of positions andto perform the control operations, that is, pass all the commands to primary apparatuses inthe form of circuit breakers via binary output boards and to supervise the switchingoperation and position.1MRK 511 287-UUS A Section 10Control251Technical manual