12.18.5 SettingsTable 429:SSCBR Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - On Operation Off / OnAccDisLevel 5.00 - 500.00 A 0.01 10.00 RMS current setting below which energyaccumulation stopsCurrExp 0.00 - 2.00 - 0.01 2.00 Current exponent setting for energy calculationRatedFaultCurr 500.00 - 75000.00 A 0.01 5000.00 Rated fault current of the breakerRatedOpCurr 100.00 - 5000.00 A 0.01 1000.00 Rated operating current of the breakerAccCurrAlmLvl 0.00 - 20000.00 - 0.01 2500.00 Setting of alarm level for accumulated currentspowerAccCurrLO 0.00 - 20000.00 - 0.01 2500.00 Lockout limit setting for accumulated currentspowerDirCoef -3.00 - -0.50 - 0.01 -1.50 Directional coefficient for CB life calculationLifeAlmLevel 0 - 99999 - 1 5000 Alarm level for CB remaining lifeOpNumRatCurr 1 - 99999 - 1 10000 Number of operations possible at rated currentOpNumFaultCurr 1 - 10000 - 1 1000 Number of operations possible at rated faultcurrentOpNumAlm 0 - 9999 - 1 200 Alarm limit for number of operationsOpNumLO 0 - 9999 - 1 300 Lockout limit for number of operationstOpenAlm 0 - 200 ms 1 40 Alarm level setting for open travel timetCloseAlm 0 - 200 ms 1 40 Alarm level setting for close travel timeOpenTimeCorr 0 - 100 ms 1 10 Correction factor for open travel timeCloseTimeCorr 0 - 100 ms 1 10 Correction factor for CB close travel timeDifTimeCorr -10 - 10 ms 1 5 Correction factor for time difference in auxiliaryand main contacts open timetSprngChrgAlm 0.00 - 60.00 s 0.01 1.00 Setting of alarm for spring charging timetPressAlm 0.00 - 60.00 s 0.01 0.10 Time delay for gas pressure alarmTPressLO 0.00 - 60.00 s 0.01 0.10 Time delay for gas pressure lockoutAccEnerInitVal 0.00 - 9999.99 - 0.01 0.00 Accumulation energy initial valueCountInitVal 0 - 9999 - 1 0 Operation numbers counter initialization valueCBRemLife 0 - 9999 - 1 5000 Initial value for the CB remaining life estimatesInactDayAlm 0 - 9999 Day 1 2000 Alarm limit value of the inactive days counterInactDayInit 0 - 9999 Day 1 0 Initial value of the inactive days counterInactHourAlm 0 - 23 Hour 1 0 Alarm time of the inactive days counter in hours1MRK 511 287-UUS A Section 12Monitoring527Technical manual