CHAPTER 13 - TROUBLESHOOTING AND MAINTENANCE149EATON PXG200E User Manual • IM02603001E Rev 5, 11-May-2012 • Firmware Version 5.03:3835Resetting Lost Passwords and IP AddressesIf you customized either the User or Admin password and have misplacedthem, follow this procedure to reset the password(s) to the factory defaultvalues.Also follow this procedure if you need to reset the IP addresses.NOTICE: All the other configuration information of your PXG200Ewill be maintained when you follow the procedure exactly. TheRestart button (Figure 164, A) restores the factory default settingsfor the static IP address, User Password and Admin Password. Allother configuration settings will be retained. Press the switch for atleast 3 seconds, but no more than 10 seconds. If you hold switch for15 seconds, the entire configuration is reset to factory values.Figure 1641. Connect the PXG200E to the Windows computer using a USB AB cable.Connect one end of the USB cable to an empty USB port on yourcomputer and the other end to the USB port on the PXG200E.2. Press the Restart button (Figure 164, A) and hold it for at least threeseconds, but less than 10 seconds. You will reset the IP address for anEthernet LAN connection to a static value of 192.168.1.1 and reset theUser and Admin passwords to the factory default values. All the otherconfiguration information of your PXG200E will be maintained.3. Release the button. The default settings will load and the unit willreboot.4. Wait at least two minutes for the PXG200E to completely reboot.5. Close the browser and reopen it.6. The PXG200E can be accessed using the following settings:User PasswordUser Name: userPassword: userAdmin PasswordUser Name: adminPassword: admin7. To customize these passwords, follow the steps in Configuration ofPassword on page 90.COM 1INCOMCOM 1INCOMRESTARTSHLDD2D1CMNA (-)B (+)+ VGND1 2PXG 200E24 VDCPXG200E_141AUPSTREAM DOWNSTREAM