CHAPTER 8 - PXG200E CONFIGURATION WEB PAGE39EATON PXG200E User Manual • IM02603001E Rev 5, 11-May-2012 • Firmware Version 5.03:3835Configuration of Downstream Communication PortsINCOM ConfigurationINCOM Configuration allows you to change parameters in the INCOMnetwork.The PXG200E supports synchronization of clocks on INCOM devices thatsupport the set time and date command.1. To access the INCOM Configuration, click on the INCOM link(Figure 30, A) in the toolbar of the PXG200E configuration web page.2. To enable the clock synchronization feature, click the ENABLE DATE/TIME SYNC box (Figure 30, B).NOTICE: The default value of the clock synchronization featureis enabled.Figure 303. Enter INCOM Receive Timeout Extend (Figure 30, C) in milliseconds.INCOM Receive Timeout Extend is a value which is added to the defaultINCOM timeout when receiving data from an INCOM device. It allowsthe user to wait longer for INCOM responses from devices who may notrespond as promptly as others.NOTICE: The default value of the INCOM Receive TimeoutExtend feature is zero.4. Enter the PowerNet IP address (Figure 30, D) (format aaa.bbb.ccc.ddd).If the PXG200E is used as an EMINT in a PowerNet device server, enterthe IP address of the PowerNet device server in this field. This willensure that the PXG200E will only respond exclusively to that PowerNetdevice server broadcast messages.5. You can SAVE ALL SETTINGS, VIEW CHANGES or DISCARD CHANGESthat you have made. For details on how to use these functions, seeCommon PXG200E Configuration Functions on page 35.PXG200E_029ABCD