CHAPTER 5 - PXG200E THEORY OF OPERATION21EATON PXG200E User Manual • IM02603001E Rev 5, 11-May-2012 • Firmware Version 5.03:3835SecuritySecurity of your power equipment is a critical issue. The PXG200Eincorporates a multi-layer set of security features to ensure your facility isnot compromised while providing you powerful connectivity capabilities.Password ProtectionThe PXG200E provides a two-level password authorization mechanism tocontrol access to data via the web user interface or from the web servicesinterface used by the Power Xpert Software.The “user level” of authorization provides “view only” access to data fromthe downstream devices. User level access does not allow for anyconfiguration changes to the PXG200E itself.The “admin level” of authorization allows for reading and setting data indownstream devices. Admin level also allows for configuration changes tothe PXG200E.NOTICE: To ensure the security of your system, immediately changethe user and admin passwords after the initial login. Refer toConfiguration of Password on page 90 for details.NOTICE: To ensure the security of your system, only provide theadmin password to those individuals who will need to configure thePXG200E or trigger device actions.Secure Web BrowsingYou have the option to encrypt exchanges with the PXG200E’s embeddedweb server. This will ensure that information and passwords exchanged withthe PXG’s web server cannot be intercepted on the LAN. To login to thesecure web server you must install a root Certificate Authority (CA). Refer toRoot Certificate Authority Installation on page 173.NOTICE: To ensure the security of your system, use the SSLconnection to the PXG200E web UI by entering HTTPS://192.168.1.1(if using default IP address) in your web browser.