CHAPTER 6 - INSTALLATION OF PXG200EEATON PXG200E User Manual • IM02603001E Rev 5, 11-May-2012 • Firmware Version 5.03:383526Wiring Connections1. Connect the power supply (Figure 13, A). WARNING! – Observeconnection polarity to prevent overheating the equipment which mayresult in a fire.2. PXG200E power LED (Figure 13, B) illuminates.3. The INCOM traffic indicator (Figure 13, C) and the COM1 trafficindicator (Figure 13, D) will flash Red, Green and Yellow / Green whilethe unit boots. This is normal.4. Connect the INCOM port (Figure 13, E) of the PXG200E to the INCOMnetwork that includes the desired “downstream” devices. For moreinformation on wiring an INCOM network, see the Eaton Electrical FieldDevices Communication Wiring Specification (TD 17513) included onyour PXG200E CD-ROM. This document is also available atwww.eaton.com/pxg.5. Connect the COM1 port (Figure 13, F) of the PXG200E to the ModbusRTU network that includes the desired “downstream” devices. For moreinformation on wiring a Modbus network see www.eaton.com/pxg.NOTICE: Observe connection polarity. See the information onCOM1 polarity on page 25.6. You are now ready to proceed and connect the unit to the Ethernet LANand / or the USB port on your computer. See the instructions inAccessing the PXG200E on page 27.Figure 13COM 1INCOMCOM 1INCOMRESTARTSHLDD2D1CMNA (-)B (+)+ VGND1 2PXG 200E24 VDCPXG200E_001AF EBDCUPSTREAM DOWNSTREAM