CHAPTER 4 - PXG200E OVERVIEW9EATON PXG200E User Manual • IM02603001E Rev 5, 11-May-2012 • Firmware Version 5.03:3835Chapter 4 PXG200E OverviewLayout of PXG200EFigure 1NOTICE: Figure 1 is a typical example of the PXG200E. Yourequipment may differ.A. VDC – Power Input - Connect to an external DC power supply that meets UL508/1131 Class 2 standards. The supply must be capable of sourcing24 VDC +/- 20% at 0.8 A.B. COM1 used to connect to Modbus RTU devices.C. INCOM, used to connect to INCOM devices.D. / . Upstream/Downstream ethernet port connections; can be daisy-chained –Connect to Local Area Network (LAN) using CAT 5 or better cable. See“Connecting a PXG200E to the Ethernet LAN” onpage 14.F. USB Configuration Port.G / H. COM1 / INCOM traffic indicator. If indicator does not blink it means that nodevices have been entered into the PXG200E device list for this port. Ifindicator blinks green it means that devices entered into the PXG200E devicelist are connected, but not responding, or the physical connection isintermittent. If indicator blinks yellow / red it means that devices entered intothe PXG200E device list are responding.I. Power Indicator (ON condition is Green).J. Restart button. This button has multiple functions:• If the button is pressed for less than 3 seconds, the PXG will perform areboot - press F5 on your computer keypad to refresh the screen.• If the button is pressed for at least 3 seconds but less than 10 seconds, thenetwork settings and passwords will be reset to their defaults.• If the button is pressed for 15 seconds or longer, all your settings will bereset to the default and the log files will be cleared. If you personalized theimage in the banner at the top of the PXG web page, it will return to thedefault image. Ensure that you have saved your configuration, usingthe Save and Restore on page 100 function, BEFORE youcontinue.COM 1INCOMCOM 1INCOMRESTARTSHLDD2D1CMNA (-)B (+)+ VGND1 2PXG 200E24 VDCPXG200E_002UPSTREAM DOWNSTREAMAB C D EJG HF I