CHAPTER 8 - PXG200E CONFIGURATION WEB PAGEEATON PXG200E User Manual • IM02603001E Rev 5, 11-May-2012 • Firmware Version 5.03:383588Configuring Modbus TCP FeatureThis screen allows you to set up the configuration of the Modbus TCPfeature of the PXG200E.1. Click on the MODBUS TCP link (Figure 87, A) in the toolbar of thePXG200E configuration web page.Figure 872. Click on the “Enable” checkbox (Figure 87, B) to enable, or disable, theconnection to the Modbus TCP server.NOTICE: Disabling the Modbus TCP server connection will alsoprohibit the use of CH Studio software for configuration ofQCPort devices.3. Click on the “Enable Writes” checkbox (Figure 87, C) to enable, ordisable, the ability to write to the Modbus TCP server.NOTICE: To ensure the security of your system, if you will not beusing Modbus TCP, uncheck the “Enable” checkbox(Figure 87, B). This will disable the Modbus TCP connection.NOTICE: If you will be reading data from Modbus TCP but notwriting data, enable the Modbus TCP connection and disablethe ability to write to the Modbus TCP server by unchecking the“Enable Writes” checkbox (Figure 87, C).4. Enter the “Timeout” value (Figure 87, E). Range is 0 to 10000milliseconds. Note that the “Timeout” value is the amount of timeallotted before the PXG200E stops processing a command.PXG200E_257ABCD