21 Analog input module XN-322-7AI-U2PT21.5 Technical data for reference outputs152 XN300 slice modules 06/16 MN050002 EN www.eaton.com21.5 Technical data for reference outputs21.6 Measurement ranges21.7 FiltersThe low-pass cutoff frequency can be configured for each voltage input chan-nel by using the appropriate register. This cutoff frequency is specified in Hzwithout any decimal places.The following settings are valid:Device version1.00 or higher 3.01 or higherNumber of channels 1Connection points per channel 6Reference voltage +10 VPermissible load perpotentiometer inputMax. permissible output current ≤ 2.50 mA ≤ 4.17 mAPotentiometer ≥ 4 kΩ ≥ 2.4 kΩMaximum operating temperature 0…60 °C 0…55 °CMaximum permissible capacitiveload100 nFShort-circuit proof Yes, maximum 1 minuteCumulative error as a percentage offull scale value±0.3 %Input 1 Value representation1 U -10…+10 V Represented as a decimal value in mVPt1000 -125…+850 °C 502.4…3904.8 Ω Represented as a decimal value inohms with one decimal place (in 1/10ohm)KTY10 -50…+150 °C 1035.9…4575.3 Ω2-6 U -10…+10V -10000…10000 Represented as a decimal value in mV7 Pt1000 -125…+850 °C 502.4…3904.8 Ω Represented as a decimal value in °Cwith one decimal place (in 1/10 °C)KTY10 -50…+150 °C 1035.9…4575.3 ΩLow-pass cut-off frequency Register valueFilter disabled (default) 0x000010 Hz 0x000A25 Hz 0x001950 Hz 0 x0032100 Hz 0x0064