23 Analog input module XN-322-10AI-TEKT23.3 Memory layout174 XN300 slice modules 06/16 MN050002 EN www.eaton.comIn the registers used to select a sensor, the low nibble (bits 0-3) is used toconfigure the lower channel (channel 1, 3, 5, 7), while the high nibble (bits 4-7) is used to configure the upper channel (channel 2, 4, 6, 8).Table 8: Sensor selection listHexadecimal value Type Measuring rangeBit 0-3Bit 4-70 hex J 0 … +690 °C1 hex K 0…+940 °C2 hex T 0…+400 °C3 hex E 0…+520 °C4 hex N 0… +1080 °C5 hex S 0…+1760 °C6 hex R 0… +1760 °C7 hex B 0… +1820 °C8 hex L 0…+680 °C9 hex U 0…+590 °CA-Fhex reserved