14 Digital output module XN-322-8DO-P0514.1 Pin assignment and status LED signalsXN300 slice modules 06/16 MN050002 EN www.eaton.com 8714.1.1 WiringFour digital outputs can be wired to the X1 connector and another four digitaloutputs can be wired to the X2 connector.14.1.2 Connecting the power supplyThe cross-sectional area of the +24 V cables used to supply power must besized for the maximum total current drawn by all the outputs.It is impermissible to apply a voltage, at any output, that exceeds the supplyvoltage by more than 0.7 V.The two 0 V pins on connector X5 are internally connected to each other.14.1.3 Connecting EN 61131-2 short-circuit proof digital outputsThe outputs are able to drive twice their rated operational current brieflywhen driving loads with higher inrush currents.Status User yellow ON The user can set the LED signals as necessary.(For example, the visualization interface can be used toset the module's LED to flash so that it is easier to findthe module inside the control panel.)OFFFLASH(200 ms ON,1000 ms OFF)FLASH(1000 ms ON,200 ms OFF)Status of output nn = 1 to 8yellow ON Output is "ON"OFF Output is "OFF"Power status fordigital outputsgreen ON The digital outputs are being powered with 24 VDCOFF The outputs are not being powered properly (under-voltage) or the system is not being powered at all. If thesystem is not being powered at all, the module statusLED will be OFF.