S1 469 Setup 469Motor Management RelaySetpointshttp://www.GEindustrial.com/multilin 5–9GE MultilinCommunications a) Serial CommunicationsThe following setpoints appear when the relay is ordered with the regular enhanced(E) option.PATH: SETPOINTS Z S1 469 SETUP ZV COMMUNICATIONSThe 469 has three (3) serial communications ports supporting a subset of theModbus protocol. The front panel RS232 has a fixed baud rate of 9600, a fixed dataframe of 1 start, 8 data, and 1 stop bits with no parity. The front port is for local useonly and responds regardless of the slave address programmed. This port may beconnected to a personal computer running EnerVista 469 Setup. The software candownload and upload setpoint files as well as upgrade the 469 firmware.For RS485 communications, each 469 must have a unique address from 1 to 254.Address 0 is the broadcast address detected by all relays. Addresses do not have tobe sequential but no two units can have the same address or errors will occur.Generally, each unit added to the link uses the next higher address starting at 1.Baud rates can be selected as 300, 1200, 2400, 4800, 9600, or 19200. The dataframe is fixed at 1 start, 8 data, and 1 stop bits, while parity is optional. Thecomputer RS485 port is a general purpose port for connection to a DCS, PLC, or PC.The auxiliary RS485 port may be used for redundancy or, it may be used to talk toauxiliary GE Multilin devices. The RS485 COM2 port is disabled if the Ethernet orDeviceNet option is ordered.b) Ethernet CommunicationsThe following setpoints appear when the relay is ordered with the Ethernet (T)option.PATH: SETPOINTS Z S1 469 SETUP ZV COMMUNICATIONSThe IP addresses are used with the Modbus protocol. Enter the dedicated IP, subnetIP, and gateway IP addresses provided by the network administrator. COMMUNICATIONS [Z] SLAVE ADDRESS:254Range: 1 to 254 in steps of 1MESSAGE COMPUTER RS485BAUD RATE: 9600Range: 300, 1200, 2400, 4800, 9600,19200MESSAGE COMPUTER RS485PARITY: NoneRange: None, Odd, EvenMESSAGE AUXILIARY RS485BAUD RATE: 9600Range: 300, 1200, 2400, 4800, 9600,19200MESSAGE AUXILIARY RS485PARITY: NoneRange: None, Odd, Even COMMUNICATIONS [Z] SLAVE ADDRESS:254Range: 1 to 254 in steps of 1MESSAGE COMPUTER RS485BAUD RATE: 9600Range: 300, 1200, 2400, 4800, 9600,19200MESSAGE COMPUTER RS485PARITY: NoneRange: None, Odd, EvenMESSAGE FRONT PORT RS232BAUD RATE: 19200Range: 300, 1200, 2400, 4800, 9600,19200MESSAGE IP ADDRESS:0.0.0.0Range: standard IP address formatMESSAGE SUBNET IP MASK:255.255.255.000Range: standard IP address formatMESSAGE GATEWAY IP ADDRESS:0.0.0.0Range: standard IP address format