A1 Status469Motor Management RelayActual Valueshttp://www.GEindustrial.com/multilin6–6 GE MultilinPhase, differential, and ground currents are recorded 1 cycle prior to the trip. Allother pre-trip data is recorded 50 ms prior to the trip. Thus some values will not berecorded upon instantaneous trips during a start if the trip is less than 50 ms.Alarm Status PATH: ACTUAL VALUES Z A1 STATUS ZV ALARM STATUSNOTE ALARM STATUS [Z] NO ALARMS Range: N/A. Message seen when noalarms are activeMESSAGE REMOTE ALARMSTATUS: ActiveRange: Active, LatchedMESSAGE PRESSURE SWITCHALARM STATUS: ActiveRange: Active, LatchedMESSAGE VIBRATION SWITCHALARM STATUS: ActiveRange: Active, LatchedMESSAGE DIG. COUNTER ALARM:1 000 000 000 UnitsRange: 1 to 9999999999. Displayscurrent value of digital counterMESSAGE TACHOMETERALARM: 3000 RPMRange: 0 to 3600 RPM. Displays currentTachometer Digital Input valueMESSAGE GENERAL SW. AALARM STATUS: ActiveRange: Active, LatchedMESSAGE THERMAL CAPACITYALARM: 100% USEDRange: 1 to 100. Thermal CapacityUsed value is shown hereMESSAGE XX.XX x FLA OVERLOADTIME TO TRIP: XXXXX sRange: 0 to 99999 s. Shows overloadlevel and estimated time to trip.MESSAGE UNDERCURRENT ALARMIa = 85 A 85% FLARange: 1 to 5000 A; 5 to 99% FLA.Lowest phase current shown.MESSAGE CURRENT UNBALANCEALARM: 15%Range: 0 to 100%. Reflects the presentunbalance levelMESSAGE GROUND FAULTALARM: 25.3 ARange: 0.1 to 5000 A. Reflects thepresent ground current levelMESSAGE STATOR RTD #1ALARM: 135°CRange: –50 to 250°CMESSAGE OPEN SENSOR ALARM:RTD # 1 2 3 4 5 6...Range: RTD with the open sensor asprogrammed for RTDs 1 to 12MESSAGE SHORT/LOW TEMP ALARMRTD # 7 8 9 10 11...Range: 1 to 12. Shows RTD with theshort/low temperature alarmMESSAGE UNDERVOLTAGE ALARMVab= 3245 V 78%Range: 0 to 20000 V; 50 to 99% ofRatedMESSAGE OVERVOLTAGE ALARMVab= 4992 V 120%Range: 0 to 20000 V; 101 to 150% ofRatedMESSAGE SYSTEM FREQUENCYALARM: 59.4 HzRange: 0.00, 20.00 to 120.00 HzMESSAGE POWER FACTORALARM PF: 0.00Range: 0.00 to 0.99 Lead or Lag, 0.00,1.00MESSAGE REACTIVE POWERALARM: +2000 kvarRange: –50000 to +50000 kvarMESSAGE UNDERPOWERALARM: 200 kWRange: –50000 to +50000 kW