S13 469 Testing 469Motor Management RelaySetpointshttp://www.GEindustrial.com/multilin 5–85GE MultilinFault Setup PATH: SETPOINTS ZV S13 469 TESTING ZV FAULT SETUPThe values entered under Fault Values will be substituted for the measured values inthe 469 when the simulation mode is “Simulate Fault”. FAULT [Z]SETUPFAULT CURRENTPHASE A: 0.00 x CTRange: 0.00 to 20.00 x CT in steps of0.01MESSAGE FAULT CURRENTPHASE B: 0.00 x CTRange: 0.00 to 20.00 x CT in steps of0.01MESSAGE FAULT CURRENTPHASE C: 0.00 x CTRange: 0.00 to 20.00 x CT in steps of0.01MESSAGE FAULT GROUNDCURRENT: 0.0 ARange: 0.0 to 5000.0 A in steps of 0.1MESSAGE FAULT VOLTAGESVLINE: 1.00 x RATEDRange: 0.00 to 1.10 x RATED in steps of0.01MESSAGE FAULT CURRENTLAGS VOLTAGE: 0°Range: 0 to 359° in steps of 1MESSAGE FAULT DIFF AMPSIDIFF: 0.00 x CTRange: 0.00 to 1.10 x RATED in steps of0.01MESSAGE FAULT STATORRTD TEMP: 40°CRange: –50 to 250°C in steps of 1MESSAGE FAULT BEARINGRTD TEMP: 40°CRange: –50 to 250°C in steps of 1MESSAGE FAULT OTHERRTD TEMP: 40°CRange: –50 to 250°C in steps of 1MESSAGE FAULT AMBIENTRTD TEMP: 40°CRange: –50 to 250°C in steps of 1MESSAGE FAULT SYSTEMFREQUENCY: 60.0 HzRange: 45.0 to 70.0 Hz in steps of 0.1MESSAGE FAULT ANALOGINPUT 1: 0%Range: 0 to 100% in steps of 1MESSAGE FAULT ANALOGINPUT 2: 0%Range: 0 to 100% in steps of 1MESSAGE FAULT ANALOGINPUT 3: 0%Range: 0 to 100% in steps of 1MESSAGE FAULT ANALOGINPUT 4: 0%Range: 0 to 100% in steps of 1