S14 Two-Speed Motor 469Motor Management RelaySetpointshttp://www.GEindustrial.com/multilin 5–91GE MultilinRefer to Voltage Dependent Overload Curves on page 5–38 for additional details onthe custom overload curves available for Speed2.MESSAGE SPEED2 TRIP AT6.50 x FLA: 8.5 sRange: 0.5 to 99999.9 in steps of 0.1MESSAGE SPEED2 TRIP AT7.00 x FLA: 7.3 sRange: 0.5 to 99999.9 in steps of 0.1MESSAGE SPEED2 TRIP AT7.50 x FLA: 6.3 sRange: 0.5 to 99999.9 in steps of 0.1MESSAGE SPEED2 TRIP AT8.00 x FLA: 5.6 sRange: 0.5 to 99999.9 in steps of 0.1MESSAGE SPEED2 TRIP AT10.0 x FLA: 5.6 sRange: 0.5 to 99999.9 in steps of 0.1MESSAGE SPEED2 TRIP AT15.0 x FLA: 5.6 sRange: 0.5 to 99999.9 in steps of 0.1MESSAGE SPEED2 TRIP AT20.0 x FLA: 5.6 sRange: 0.5 to 99999.9 in steps of 0.1MESSAGE SPEED2 MIN ALLOWABLELINE VOLTAGE: 80%Range: 70 to 95% in steps of 1MESSAGE SPEED2 ISTALL @ MINVline: 4.80 x FLARange: 2.00 to 15.00 x FLA in steps of0.01MESSAGE SPEED2 SAFE STALL @MIN Vline: 20.0 sRange: 0.5 to 999.9 s in steps of 0.1MESSAGE SPEED2 ACL INTERSECT@MIN Vline: 3.80 x FLARange: 2.00 to SPEED2 ISTALL @ MINVLINE – 0.01 in steps of 0.01MESSAGE SPEED2 ISTALL @ 100%Vline: 6.00 x FLARange: 2.00 to 15.00 x FLA in steps of0.01MESSAGE SPEED2 SAFE STALL @100% Vline: 10.0 sRange: 0.5 to 999.9 s in steps of 0.1MESSAGE SPEED2 ACL INTERSECT@100% Vline: 5.00xFLARange: 2.00 to SPEED2 ISTALL @ 100%VLINE – 0.01 in steps of 0.01