A1 Status 469Motor Management RelayActual Valueshttp://www.GEindustrial.com/multilin 6–7GE MultilinAny active alarms may be viewed here.The various alarm and alarm status actual values reflect the Alarm Name asprogrammed in the first line of the message. The status is “Active” if the conditionthat caused the alarm is still present.If the 469 chassis is only partially engaged with the case, the ALARM, 469 NOTINSERTED PROPERLY service alarm appears after 1 second. Secure the chassis handleto ensure that all contacts mate properly.MESSAGE TRIP COUNTERALARM: 25 TripsRange: 1 to 10000 TripsMESSAGE STARTER FAILURE:Trip Coil SuperRange: Trip Coil Super, WeldedContactor, Breaker FailureMESSAGE CURRENT DEMANDALARM: 1053 ARange: 1 to 10000 AMESSAGE kW DEMANDALARM: 505 kWRange: –50000 to +50000 kWMESSAGE kvar DEMANDALARM: –2000 kvarRange: –50000 to +50000 kvarMESSAGE kVA DEMANDALARM: 2062 kVARange: 0 to 50000 kVAMESSAGE ANALOG I/P 1ALARM: 201 UnitsRange: –50000 to +50000MESSAGE EMERGENCY RESTART:Trip Still PresentRange: Trip Still Present, Block StillPresent, No Trips & No BlocksMESSAGE ALARM, 469 NOTINSERTED PROPERLYRange: N/AMESSAGE 469 NOT IN SERVICENot ProgrammedRange: Not Programmed, OutputRelays Forced, Analog OutputForced, Test Switch ShortedMESSAGE RTD #1HI ALARM: 135°CRange: 1 to 250°CMESSAGE ANALOG 1-2ALARM: 50%Range: 0 to 999 (% Diff) or 0 to 99999(Abs Diff)MESSAGE ANALOG 3-4ALARM: 50%Range: 0 to 999 (% Diff) or 0 to 99999(Abs Diff)MESSAGE OVERTORQUEALARM: 0.00Range: 0.00 to 999999.9 Nm