S9 Voltage Elements 469Motor Management RelaySetpointshttp://www.GEindustrial.com/multilin 5–67GE MultilinFrequency PATH: SETPOINTS ZV S9 VOLTAGE ELEM. ZV FREQUENCYOnce the frequency of the phase AN or AB voltage (depending on wye or deltaconnection) is out of range of the overfrequency and underfrequency setpoints, atrip or alarm will occur.This feature may be useful for load shedding applications on large motors. It couldalso be used to load shed an entire feeder if the trip was assigned to an upstreambreaker. FREQUENCY [Z] FREQUENCYALARM: OffRange: Off, Latched, UnlatchedMESSAGE ASSIGN ALARM RELAYS:AlarmRange: Alarm, Alarm & Auxiliary2,Alarm & Aux2 & Aux3, Alarm &Auxiliary3, Auxiliary2, Aux2 &Aux3, Auxiliary3MESSAGE OVER FREQUENCYALARM LEVEL: 60.50 HzRange: 25.01 to 70.00 Hz in steps of0.01MESSAGE UNDER FREQUENCYALARM LEVEL: 59.50 HzRange: 20.00 to 60.00 Hz in steps of0.01MESSAGE FREQUENCYALARM DELAY: 1.0 sRange: 0.0 to 60.0 s in steps of 0.1MESSAGE FREQUENCYALARM EVENTS: OffRange: On, OffMESSAGE FREQUENCYTRIP: OffRange: Off, Latched, UnlatchedMESSAGE ASSIGN TRIP RELAYS:TripRange: Trip, Trip & Auxiliary2, Trip &Aux2 & Aux3, Trip & Auxiliary3MESSAGE OVER FREQUENCYTRIP LEVEL: 60.50 HzRange: 25.01 to 70.00 Hz in steps of0.01MESSAGE UNDER FREQUENCYTRIP LEVEL: 59.50 HzRange: 20.00 to 60.00 Hz in steps of0.01MESSAGE FREQUENCYTRIP DELAY: 1.0 sRange: 0.0 to 60.0 s in steps of 0.1