3.2.3.2 EARTH FAULT FIXED REACTANCE LINE TILTINGEach zone has an independent setting to set the tilt angle (σ) of the Impedance Reach line of the quadrilateralcharacteristic. If dynamic tilting is disabled, the characteristic uses this setting to apply a fixed tilt to the top line.The tilting angle is with reference to the fault current I, and is defined by:Tilt angle = setting (σ) =Ð Iph/IThe setting range is +/- 30°. A negative angle sets a downward tilt and a positive angle sets an upward tilt.Operation occurs when the operating current I lags the polarizing current Iph.The Impedance Reach line of the characteristic in the Z1 plane is shown in the following diagram:+R+jXZ IVZIV V02731Z1-plane Ð jeIIphFigure 54: Impedance Reach line in Z1 planeFor all V/I vectors below the Impedance Reach line, the following condition is true:Ð (V/I-Z) ≤ σor Ð (V – I.Z) ≤ I + σIf mutual compensation is not applied, for an earth-fault loopV = VphandI = Iph + kZN.INso the signals fed into comparator are:S1 = Vph – Iph.ZreplicaS2 = IphÐ σwhere: Zreplica is the replica forward reachThe impedance below the Impedance Reach line is detected when the angle between the signals is less than 0°:For products that have mutual compensation, if the mutual compensation is applied, thenZreplica =Z(1+kZN.IN/Iph+kZM.IM/Iph).Chapter 7 - Distance Protection P446SV132 P446SV-TM-EN-1