If Res LO by CB IS is set to Enabled, a lockout is reset if the circuit breaker is successfully closed manually. Forthis, the circuit breaker must remain closed long enough so that it enters the “In Service” state.If Res LO by UI is set to Enabled, the circuit breaker lockout can be reset from a user interface using the resetcircuit breaker lockout command in the CB CONTROL column.If Res LO by NoAR is set to Enabled, the circuit breaker lockout can be reset by temporarily generating an ARdisabled signal.If Res LO by TDelay is set to Enabled, the circuit breaker lockout is automatically reset after a time delay set inthe LO Reset Time setting.If Res LO by ExtDDB is Enabled, the circuit breaker lockout can be reset by activation of an external inputmapped in the PSL to the relevant reset lockout DDB signal.Chapter 16 - Monitoring and Control P446SV424 P446SV-TM-EN-1