P446SV Appendix B -Settings and SignalsP446SV-TM-EN-1 B31MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONSDESCRIPTIONPhase angle difference between selected phase ("C/S Input" 0A 0F) of Line VT input and applied "CB2 CS" VT input voltage under healthysystem conditionsCB2 CS VT Mag 0A 24 1 From 0.2 to 3 in steps of 0.01[Courier Number]Ratio of voltage magnitudes of selected phase ("C/S Input" 0A 0F) of Line VT input and applied "CB2 CS" VT input voltage under healthysystem conditionsRECORD CONTROL 0B 00This column contains settings for Record ControlsAlarm Event 0B 04 EnabledDisabledEnabled[Indexed String]Disabling this setting means that all the occurrences that produce an alarm will result in no event being generated.Relay O/P Event 0B 05 EnabledDisabledEnabled[Indexed String]Disabling this setting means that no event will be generated for any change in logic state.Opto Input Event 0B 06 EnabledDisabledEnabled[Indexed String]Disabling this setting means that no event will be generated for any change in logic input state.General Event 0B 07 EnabledDisabledEnabled[Indexed String]Disabling this setting means that no General Events will be generatedFault Rec Event 0B 08 EnabledDisabledEnabled[Indexed String]Disabling this setting means that no event will be generated for any fault that produces a fault recordMaint Rec Event 0B 09 EnabledDisabledEnabled[Indexed String]Disabling this setting means that no event will be generated for any occurrence that produces a maintenance record.Protection Event 0B 0A EnabledDisabledEnabled[Indexed String]Disabling this setting means that any operation of protection elements will not be logged as an eventDDB 31 - 0 0B 40 0xFFFFFFFFHigh order word of long stored in 1st registerLow order word of long stored in 2nd register[Binary Flag (32-Bit)]Chooses whether any individual DDBs should be deselected as a stored event, by setting the relevant bit to 0 (zero). Typically used forrepetitive recurrent changes such as an Opto input assigned for Minute Pulse clock synchronizing.DDB 63 - 32 0B 41 0xFFFFFFFFHigh order word of long stored in 1st registerLow order word of long stored in 2nd register[Binary Flag (32-Bit)]Chooses whether any individual DDBs should be deselected as a stored event, by setting the relevant bit to 0 (zero). Typically used forrepetitive recurrent changes such as an Opto input assigned for Minute Pulse clock synchronizing.DDB 95 - 64 0B 42 0xFFFFFFFFHigh order word of long stored in 1st registerLow order word of long stored in 2nd register[Binary Flag (32-Bit)]Chooses whether any individual DDBs should be deselected as a stored event, by setting the relevant bit to 0 (zero). Typically used forrepetitive recurrent changes such as an Opto input assigned for Minute Pulse clock synchronizing.DDB 127 - 96 0B 43 0xFFFFFFFFHigh order word of long stored in 1st registerLow order word of long stored in 2nd register[Binary Flag (32-Bit)]Chooses whether any individual DDBs should be deselected as a stored event, by setting the relevant bit to 0 (zero). Typically used forrepetitive recurrent changes such as an Opto input assigned for Minute Pulse clock synchronizing.DDB 159 - 128 0B 44 0xFFFFFFFFHigh order word of long stored in 1st registerLow order word of long stored in 2nd register[Binary Flag (32-Bit)]Chooses whether any individual DDBs should be deselected as a stored event, by setting the relevant bit to 0 (zero). Typically used for