P446SV Appendix B -Settings and SignalsP446SV-TM-EN-1 B101MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONSDESCRIPTIONThis setting is visible only when ground characteristic is set to ‘Quad’.Z1 Tilt Top Line 32 54 -3 From -30 to 30 in steps of 1[Courier Number (angle)]Setting of the zone 1 tilt angle. Minus angle tilts the reactance line downwards This setting is visible only when the above setting is visible.kZN1 Res. Comp. 32 55 1 From 0 to 10 in steps of 0.01[Courier Number]Setting of Z1 residual compensation magnitude.kZN1 Res. Angle 32 56 0 From -180 to 90 in steps of 0.1[Courier Number (angle)]Setting of Z1 residual compensation angle.kZm1 Mut. Comp. 32 57 1 From 0 to 10 in steps of 0.01[Courier Number]Setting of Z1 mutual compensation magnitude.kZm1 Mut. Angle 32 58 0 From -180 to 90 in steps of 0.1[Courier Number (angle)]Setting of Z1 mutual compensation angle.R1 Gnd Resistive 32 59 8 From 0.05*v1/I1 to 500*V1/I1 in steps of 0.01*V1/I1[Courier Number (impedance)]Setting for Z1 ground resistive reach. This setting is only visible if Quad is selected.Z1 Sensit Ignd>1 32 5B 0.075 From 0.05*I1 to 2*I1 in steps of 0.005*I1[Courier Number (current)]Current sensitivity setting for Z1 that must be exceeded in faulted phase and the neutral if Z1 is to operate.Z2 Gnd. Reach 32 60 15 From 0.05*v1/I1 to 500*V1/I1 in steps of 0.01*V1/I1[Courier Number (impedance)]Setting for Z2 reach.Z2 Gnd. Angle 32 61 70 From 20 to 90 in steps of 1[Courier Number (angle)]Setting of line angle (positive sequence) for zone 2.Z2 Dynamic Tilt 32 63 EnabledDisabledEnabled[Indexed String]Setting that enables or disables zone 2 top reactance line dynamic tilting. If set enabled, the top line angle will be automatically shifted bythe angle difference between the fault current and negative sequence current, starting from the ‘Z2 Tilt top line’ angle setting – see the nextcell. The zone 2, as over-reaching zone, is allowed only to tilt up. If Dynamic tilting is disabled, the top line will be shifted by the ‘Z2 Tilt topline’ setting (Predetermined tilting by fixed angle).This setting is visible only when ground characteristic is set to ‘Quad’.Z2 Tilt Top Line 32 64 -3 From -30 to 30 in steps of 1[Courier Number (angle)]Setting of the zone 2 tilt angle. Minus angle tilts the reactance line downwards This setting is visible only when the above setting is visible.kZN2 Res. Comp. 32 65 1 From 0 to 10 in steps of 0.01[Courier Number]Setting of Z2 residual compensation magnitude.kZN2 Res. Angle 32 66 0 From -180 to 90 in steps of 0.1[Courier Number (angle)]Setting of Z2 residual compensation angle.kZm2 Mut. Comp. 32 67 1 From 0 to 10 in steps of 0.01[Courier Number]Setting of Z2 mutual compensation magnitude.kZm2 Mut. Angle 32 68 0 From -180 to 90 in steps of 0.1[Courier Number (angle)]Setting of Z2 mutual compensation angle.R2 Gnd Resistive 32 69 15 From 0.05*v1/I1 to 500*V1/I1 in steps of 0.01*V1/I1[Courier Number (impedance)]Setting for Z2 ground resistive reach.Z2 Sensit Ignd>2 32 6B 0.075 From 0.05*I1 to 2*I1 in steps of 0.005*I1[Courier Number (current)]Zone 2 current sensitivity.Z3 Gnd. Reach 32 70 25 From 0.05*v1/I1 to 500*V1/I1 in steps of 0.01*V1/I1[Courier Number (impedance)]Setting for Z3 reach.