Signal Name Source Destination DescriptionBARCB2 Autoreclose Lockout (55) Leader/Follower (7) Block Autoreclose for CB2CB13PDTComp 3-phase AR Dead Time (25)CB Autoclose (32)Prepare Reclaim Initiation (34)CB Healthy and System Check Timers (39)Three-pole Autoreclose dead time iscomplete for CB1CB13PFTComp Follower 3-phase CB ARTime (29)CB Autoclose (32)Prepare Reclaim Initiation (34)CB Healthy and System Check Timers (39)Three-pole Autoreclose follower time iscomplete for CB1CB1ARSucc Successful AR Signals (36) AR Reset Successful (37)CB1 AR In Progress (16) Autoreclose successful for CB1CB1FARIP CB1 AR In Progress (16) Autoreclose Lockout (55)Reclaim Time (35)Autoreclose in progress for CB1 acting asfollowerCB1LARIP CB1 AR In Progress (16) Autoreclose Lockout (55)Reclaim Time (35)Autoreclose in progress for CB1 acting asleaderCB1OP1P CB Open (3)Dead Time Start Enable (22)Follower 1-phase CB AR Time (28)CB Autoclose (32)Successful AR Signals (36)CB1 is open on 1 phaseCB1OP2/3P CB Open (3)CB1 AR In Progress (16)3-phase AR cycle selection (21)Follower 1-phase CB AR Time (28)Successful AR Signals (36)CB1 is open on 2 or 3 phasesCB1OPAny CB Open (3) Autoreclose Lockout (55) CB1 is open on 1, 2 or 3 phasesCB1SPOK CB1 is OK for single-phase autoreclosure(either as leader or follower)CB1CRLo CB In Service (4) Reset CB Lockout (57) Reset CB1 lockoutCB1F3PAR 3-phase AR cycle selection(21)Follower 3-phase CB AR Time (29)CB Autoclose (32)Three-phase Autoreclose is active for CB1as followerCB1F3PAROK AR Modes Enable (9)CB1 AR In Progress (16)3-phase AR cycle selection (21)Autoreclose Lockout (55)CB1 is OK to perform three-phaseAutoreclose as followerCB1FSPAR 1-phase AR Cycle Selection(19)Follower CB AR Enable (27Follower 1-phase CB AR Time (28)Follower 3-phase CB AR Time (29)CB Autoclose (32)Single-phase Autoreclose is in progress forCB1 as followerCB1FSPAROK AR Modes Enable (9)Force 3-phase Trip (10), 1-phase AR CycleSelection (19)3-phase AR cycle selection (21)Autoreclose Lockout (55)CB1 is OK to perform single-phaseAutoreclose as followerCB1L3PAR 3-phase AR cycle selection(21)1-phase AR Cycle Selection (19)3-phase AR Dead Time (25)CB Autoclose (32)CB Healthy and System Check Timers (39)Three-phase Autoreclose is active for CB1(CB1 as leader)CB1L3PAROK AR Modes Enable (9)CB1 AR In Progress (16)3-phase AR cycle selection (21),Autoreclose Lockout (55)CB1 is OK to perform three-phaseAutoreclose (as leader)CB1LFRC Leader/FollowerLogic 1 & 2 (7)Leader/FollowerLogic 1 & 2 (7)Follower 1-phase CB AR Time (28)Follower 3-phase CB AR Time (29)Reclaim Time (35)CB1 failed to reclose (as leader)P446SV Chapter 11 - AutorecloseP446SV-TM-EN-1 273