11 General Class Objects62 YASKAWA ELECTRIC SIEP C730600 43A YASKAWA AC Drive-Option Card DeviceNet Technical Manual2Polled I/O1 StateStatus of the instance.00: Network not found or not yetconnected.01: Online, awaiting connection from themaster.02: Waiting to write the connection ID.03: Connected successfully.04: Timeout.{ – Byte – 32 Instance typeThe instance type.00: Explicit message01: I/O message{ – Byte – 13 Transport class trigger Defines behavior of the connection. { – Byte – –4 Produced connectionID The label used in the comm. header for thedrive.Set once the comm. connection is complete.{ – Word – –5 Consumed connectionID { – Word – –6 Initial commcharacteristics Code for the comm. type. { – Byte – –7 Produced connectionsizeMaximum number of bytes that can betransmitted. { – Byte – 48 Consumed connectionsize Maximum number of bytes received. { – Byte – 49 Expected packet rateThe time to timeout after receiving acomm. request. Rounds up to the nearest 10ms.{ { Word<1>0 ~65535 012 Watchdog time-outactionAction taken after timeout.00: Save value until reset or power is shutoff01: Auto delete02: Restart while remaining connected{ { Byte 0 ~ 2 013 Produced connectionpath lengthNumber of bytes for the transmissionconnection path. { – Word<2> – 614 Produced connectionpathSpecifies the application object whose datawill be produced by this ConnectionObject.{ { Array<2> – 20h 04h 24h47h 30h 03h15 Consumed connectionpath lengthNumber of bytes in the consumedconnection path. { – Word<2> – 616 Consumed connectionpathSpecifies the Application Object that willreceive data consumed by this ConnectionObject.{ { Array<2> – 20h 04h 24h15h 30h 03h100 Produced connectionpathNumber of bytes in the consumedconnection path. { { Byte – 71101 Consumed connectionpathSpecifies the Application Object that willreceive data consumed by this ConnectionObject.{ { Byte3 – 21InstanceID Attribute Name Description Get Set Size Range Default