Name Type Default DescriptionENMULT4 BOOLEAN 0 When activated, the current multiplier is in use forstep4CBPOS BOOLEAN 0 Breaker positionCLOSECB BOOLEAN 0 Breaker close commandOPENCB BOOLEAN 0 Breaker open commandPID-6967-OUTPUTSIGNALS v3Table 84:EF4PTOC Output signalsName Type DescriptionTRIP BOOLEAN General trip signalTRIN1 BOOLEAN Trip signal from step 1TRIN2 BOOLEAN Trip signal from step 2TRIN3 BOOLEAN Trip signal from step 3TRIN4 BOOLEAN Trip signal from step 4TRSOTF BOOLEAN Trip signal from earth fault switch onto faultfunctionSTART BOOLEAN General start signalSTIN1 BOOLEAN Start signal step 1STIN2 BOOLEAN Start signal step 2STIN3 BOOLEAN Start signal step 3STIN4 BOOLEAN Start signal step 4STSOTF BOOLEAN Start signal from earth fault switch onto faultfunctionSTFW BOOLEAN Start signal forward directionSTRV BOOLEAN Start signal reverse direction2NDHARMD BOOLEAN 2nd harmonic block signal8.4.5 Settings IP11454-1 v2PID-6967-SETTINGS v3Table 85:EF4PTOC Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / OnEnDir DisableEnable- - Enable Enabling the Directional calculationAngleRCA -180 - 180 Deg 1 65 Relay Characteristic Angle (RCA)polMethod VoltageCurrentDual- - Voltage Type of polarizationUPolMin 1 - 100 %UB 1 1 Minimum voltage level for polarization in% of UBaseTable continues on next pageSection 8 1MRK 505 394-UEN ACurrent protection184 Line differential protection RED650 2.2 IECTechnical manual