8.7.3 Function block M17149-3 v6CCPDSCI3P*BLOCKBLKDBYARCLOSECMDOPENCMDEXTPDINDPOLE1OPNPOLE1CLPOLE2OPNPOLE2CLPOLE3OPNPOLE3CLTRIPSTARTIEC13000305-1-en.vsdIEC13000305 V1 EN-USFigure 98: CCPDSC function block8.7.4 SignalsPID-3525-INPUTSIGNALS v8Table 109:CCPDSC Input signalsName Type Default DescriptionI3P GROUPSIGNAL- Three phase currentsBLOCK BOOLEAN 0 Block of functionBLKDBYAR BOOLEAN 0 Block of function at CB single phase auto re-closing cycleCLOSECMD BOOLEAN 0 Close order to CBOPENCMD BOOLEAN 0 Open order to CBEXTPDIND BOOLEAN 0 Pole discordance signal from CB logicPOLE1OPN BOOLEAN 1 Pole one opened indication from CBPOLE1CL BOOLEAN 0 Pole one closed indication from CBPOLE2OPN BOOLEAN 1 Pole two opened indication from CBPOLE2CL BOOLEAN 0 Pole two closed indication from CBPOLE3OPN BOOLEAN 1 Pole three opened indication from CBPOLE3CL BOOLEAN 0 Pole three closed indication from CBPID-3525-OUTPUTSIGNALS v8Table 110:CCPDSC Output signalsName Type DescriptionTRIP BOOLEAN Trip signal to CBSTART BOOLEAN Trip condition TRUE, waiting for time delaySection 8 1MRK 505 394-UEN ACurrent protection220 Line differential protection RED650 2.2 IECTechnical manual