Data Value Data Valid Comm Valid TestIncoming data with q=test+oldData 0 0 1 1Receiver in block 0 0 1 0Receiver in block andcommunication error0 0 0 0Receiver in test mode and incomingdata with q= NormalUpdated 1 1 0Receiver in test mode and incomingdata with q= TestUpdated 1 1 1Communication Error 0 0 0 0At least one of the inputs of this GOOSE block must be linkedeither in SMT by means of a cross or in ACT by means of aGOOSE connection (if easy GOOSE engineering is enabled) toreceive any data. Only those outputs whose source input is linked/connected will be updated.The implementation for IEC 61850 quality data handling isrestricted to a simple level. If quality data validity is GOOD thenthe DVALIDx output will be HIGH. If quality data validity isINVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLDDATA then the DVALIDx output will be LOW.18.4.13 GOOSE function block to receive a switching deviceGOOSEXLNRCV18.4.13.1 IdentificationGUID-4B23D0CF-F298-4BBC-B833-1B8CC98D1604 v1Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberGOOSE function block to receive aswitching deviceGOOSEXLNRCV - -18.4.13.2 Functionality GUID-5AC7DE11-CB95-4565-A8AE-FB23D59FD717 v1The GOOSE XLN Receive component is used to collect information from anotherdevice’s XCBR/XSWI logical node sent over process bus via GOOSE. TheGOOSE XLN Receive component includes 12 different outputs (and theirrespective channel valid bits) with defined names to ease the 61850 mapping of theGOOSE signals in the configuration process.1MRK 505 394-UEN A Section 18Station communicationLine differential protection RED650 2.2 IEC 663Technical manual