Function Range or value AccuracyReclaim time ”tReclaim” (0.00-6000.00) s ±0.2% or ±15 mswhichever is greaterMaximum wait time for release from master“tWaitForMaster”(0.00-6000.00) s ±0.2% or ±15 mswhichever is greaterReset time for reclosing inhibit “tInhibit” (0.000-60.000) s ±0.2% or ±45 mswhichever is greaterWait time after close command beforeproceeding to next shot “tAutoContWait”(0.000-60.000) s ±0.2% or ±45 mswhichever is greaterMaximum wait time for fulfilled synchrocheckconditions “tSync”(0.00-6000.00) s ±0.2% or ±45 mswhichever is greaterDelay time before indicating successfulreclosing “tSuccessful”(0.000-60.000) s ±0.2% or ±50 mswhichever is greaterMaximum wait time for circuit breaker closingbefore indicating unsuccessful “tUnsucCl”(0.00-6000.00) s ±0.2% or ±45 mswhichever is greater12.3 Interlocking IP15572-1 v212.3.1 Logical node for interlocking SCILO IP14138-1 v212.3.1.1 IdentificationGUID-3EC5D7F1-FDA0-4F0E-9391-08D357689E0C v3Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberLogical node for interlocking SCILO - 312.3.1.2 Functionality M15048-3 v6The Logical node for interlocking SCILO function is used to enable a switchingoperation if the interlocking conditions permit. SCILO function itself does notprovide any interlocking functionality. The interlocking conditions are generated inseparate function blocks containing the interlocking logic.12.3.1.3 Function block M15049-3 v6IEC05000359-2-en.vsdSCILOPOSOPENPOSCLOSEOPEN_ENCLOSE_ENEN_OPENEN_CLOSEIEC05000359 V2 EN-USFigure 164: SCILO function blockSection 12 1MRK 505 394-UEN AControl346 Line differential protection RED650 2.2 IECTechnical manual