22.2.7.6 Technical data SEMOD55338-1 v1M12576-1 v9Table 623:BIM - Binary input moduleQuantity Rated value Nominal rangeBinary inputs 16 -DC voltage, RL 24/30 V48/60 V110/125 V220/250 VRL ±20%RL ±20%RL ±20%RL ±20%Power consumption24/30 V, 50 mA48/60 V, 50 mA110/125 V, 50 mA220/250 V, 50 mA220/250 V, 110 mAmax. 0.05 W/inputmax. 0.1 W/inputmax. 0.2 W/inputmax. 0.4 W/inputmax. 0.5 W/input-Counter input frequency 10 pulses/s max -Oscillating signal discriminator Blocking settable 1–40 HzRelease settable 1–30 HzDebounce filter Settable 1–20 msM50609-2 v7Table 624:BIM - Binary input module with enhanced pulse counting capabilitiesQuantity Rated value Nominal rangeBinary inputs 16 -DC voltage, RL 24/30 V48/60 V110/125 V220/250 VRL ±20%RL ±20%RL ±20%RL ±20%Power consumption24/30 V48/60 V110/125 V220/250 Vmax. 0.05 W/inputmax. 0.1 W/inputmax. 0.2 W/inputmax. 0.4 W/input-Counter input frequency 10 pulses/s max -Balanced counter input frequency 40 pulses/s max -Oscillating signal discriminator Blocking settable 1–40 HzRelease settable 1–30 HzDebounce filter Settable 1-20 ms22.2.8 Binary output modules (BOM) IP14536-1 v122.2.8.1 Introduction M6938-3 v4The binary output module has 24 independent output relays and is used for tripoutput or any signaling purpose.Section 22 1MRK 505 394-UEN AIED hardware824 Line differential protection RED650 2.2 IECTechnical manual