Function block First LON address infunction blockEVENT:17 1280EVENT:18 1296EVENT:19 1312EVENT:20 1328Event masks M15083-78 v4Event mask for each input can be set individually from Parameter Setting Tool(PST) under: Settings/IED settings/ Monitoring / Event Function or viaparameter setting tool (PST) as follows:• No events• OnSet, at pick-up of the signal• OnReset, at drop-out of the signal• OnChange, at both pick-up and drop-out of the signal• AutoDetect, the EVENT function makes the reporting decision (reportingcriteria for integers has no semantic, prefer to be set by the user)Single indication M15083-123 v3Directly connected binary IO signal via binary input function block (SMBI) isalways reported on change, no changed detection is done in the EVENT functionblock. Other Boolean signals, for example a start or a trip signal from a protectionfunction is event masked in the EVENT function block.Double indications M15083-126 v3Double indications can only be reported for the first 8 inputs on an EVENTfunction block.• 00 generates an intermediate event with the read status 0• 01 generates an open event with the read status 1• 10 generates a close event with the read status 2• 11 generates an undefined event with the read status 3Analog value M15083-135 v4All analog values are reported cyclic. The reporting interval is taken from theconnected function if there is a limit supervised signal. Otherwise it is taken fromthe EVENT function block.Command handling M15083-80 v4Commands are transferred using transparent SPA-bus messages. The transparentSPA-bus message is an explicit LON message which contains an ASCII charactermessage following the coding rules of the SPA-bus protocol. The message is sentusing explicit messages with message code 41H and using acknowledged transportservice.Both the SPA-bus command messages (R or W) and the reply messages (D, A orN) are sent using the same message code. It is mandatory that one device sends outSection 18 1MRK 505 394-UEN AStation communication682 Line differential protection RED650 2.2 IECTechnical manual