Name Type DescriptionCOUNT3P3 INTEGER Number of three-phase shot 3 reclosingsCOUNT3P4 INTEGER Number of three-phase shot 4 reclosingsCOUNT3P5 INTEGER Number of three-phase shot 5 reclosingsCOUNTAR INTEGER Number of total reclosing shotsMODE INTEGER Integer output for reclosing modeABORTED BOOLEAN General abortSYNCFAIL BOOLEAN AR sequence is aborted by synchrocheckconditions not fulfilledINHIBOUT BOOLEAN AR sequence is aborted via INHIBIT input12.2.5 SettingsPID-6796-SETTINGS v2Table 173:SMBRREC Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / OnExternalCtrl OffOn- - Off To be set On if AR is to be used withexternal controlARMode 3 phase1/2/3ph1/2ph1ph+1*2ph1/2ph+1*3ph1ph+1*2/3ph- - 1/2/3ph AR mode selectiont1 1Ph 0.000 - 120.000 s 0.001 1.000 Dead time for shot 1, single-phasereclosingt1 3Ph 0.000 - 120.000 s 0.001 6.000 Dead time for shot 1, delayed three-phase reclosing with synchrocheckconditionst1 3PhHS 0.000 - 120.000 s 0.001 0.400 Dead time for shot 1, high speed three-phase reclosingtReclaim 0.00 - 6000.00 s 0.01 60.00 Reclaim timetSync 0.00 - 6000.00 s 0.01 30.00 Maximum wait time for fulfilledsynchrocheck conditionstLongStartInh 0.000 - 60.000 s 0.001 0.200 Maximum allowed start pulse durationtPulse 0.000 - 60.000 s 0.001 0.200 Circuit breaker closing pulse durationtCBClosedMin 0.00 - 6000.00 s 0.01 5.00 Minimum time that circuit breaker mustbe closed before new sequence isallowedtUnsucCl 0.00 - 6000.00 s 0.01 30.00 Maximun wait time for circuit breakerclosing before indicating unsuccessfulTable continues on next pageSection 12 1MRK 505 394-UEN AControl324 Line differential protection RED650 2.2 IECTechnical manual