18.4.10.2 Functionality GUID-0C99A106-C131-45D3-9B81-6B188E35EB34 v3GOOSESPRCV is used to receive a single point value using IEC 61850 protocolvia GOOSE.18.4.10.3 Function block GUID-A414F31A-323F-4684-BADA-46F9C5E2B0E8 v1IEC10000248-2-en.vsdGOOSESPRCVBLOCK^SRCSPOUT^SPOUTDATAVALIDCOMMVALIDTESTIEC10000248 V2 EN-USFigure 323: GOOSESPRCV function block18.4.10.4 SignalsGUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1Except for the BLOCK input, the rest of the inputs of this GOOSEfunction block are used for GOOSE connections. Theseconnections are visible and possible to make only if Easy GOOSEengineering is enabled. For instructions on how to enable EasyGOOSE engineering in PCM600, refer to the Engineering Manual.PID-6832-INPUTSIGNALS v3Table 473:GOOSESPRCV Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of functionSRCSPOUT BOOLEAN 0 Source to single point outputPID-6832-OUTPUTSIGNALS v3Table 474:GOOSESPRCV Output signalsName Type DescriptionSPOUT BOOLEAN Single point outputDATAVALID BOOLEAN Data valid for single point outputCOMMVALID BOOLEAN Communication valid for single point outputTEST BOOLEAN Test output18.4.10.5 SettingsPID-6832-SETTINGS v3Table 475:GOOSESPRCV Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/OnSection 18 1MRK 505 394-UEN AStation communication654 Line differential protection RED650 2.2 IECTechnical manual