Name Type DescriptionAPP15VAL BOOLEAN Apparatus 15 position is validCOMMVALID BOOLEAN Communication ValidTEST BOOLEAN Test Output18.4.11.4 Settings SEMOD173168-1 v2PID-6831-SETTINGS v3Table 478:GOOSEINTLKRCV Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/On18.4.11.5 Operation principle GUID-7275CFBA-F1FE-496A-A9A1-724139DB2081 v1The APPxVAL output will be HIGH if the incoming message is with valid data.The COMMVALID output will become LOW when the sending IED is under totalfailure condition and the GOOSE transmission from the sending IED does nothappen.The TEST output will go HIGH if the sending IED is in test mode.Data Value Data Valid Comm Valid TestIncoming data with q=Normal Updated 1 1 0Incoming data with q=oldData 0 0 1 0Incoming data with q=Invalid 0 0 1 0Incoming data with q=test 0 0 1 1Incoming data with q=test+oldData 0 0 1 1Receiver in block 0 0 1 0Receiver in block andcommunication error0 0 0 0Receiver in test mode and incomingdata with q= NormalUpdated 1 1 0Receiver in test mode and incomingdata with q= TestUpdated 1 1 1Communication Error 0 0 0 0At least one of the inputs of this GOOSE block must be linkedeither in SMT by means of a cross or in ACT by means of aGOOSE connection (if easy GOOSE engineering is enabled) toreceive any data. Only those outputs whose source input is linked/connected will be updated.1MRK 505 394-UEN A Section 18Station communicationLine differential protection RED650 2.2 IEC 659Technical manual