22.5.5 Type tests according to standard IP16288-1 v1M16706-1 v9Table 655:Electromagnetic compatibilityTest Type test values Reference standards1 MHz burst disturbance 2.5 kV IEC 60255-26100 kHz slow dampedoscillatory wave immunitytest2.5 kV IEC 61000-4-18, Class IIIRing wave immunity test,100 kHz2-4 kV IEC 61000-4-12, Class IVSurge withstand capabilitytest2.5 kV, oscillatory4.0 kV, fast transientIEEE/ANSI C37.90.1Electrostatic dischargeDirect applicationIndirect application15 kV air discharge8 kV contact discharge8 kV contact dischargeIEC 60255-26IEC 61000-4-2, Class IVElectrostatic dischargeDirect applicationIndirect application15 kV air discharge8 kV contact discharge8 kV contact dischargeIEEE/ANSI C37.90.1Fast transient disturbance 4 kV(SFP galvanic RJ45: 2kV)IEC 60255-26, Zone ASurge immunity test 2-4 kV, 1.2/50 mshigh energyIEC 60255-26, Zone APower frequency immunitytest150-300 V, 50 Hz IEC 60255-26, Zone AConducted common modeimmunity test15 Hz-150 kHz IEC 61000-4-16, Class IVPower frequency magneticfield test1000 A/m, 3 s100 A/m, cont.IEC 61000-4-8, Class VPulse magnetic fieldimmunity test1000 A/m IEC 61000–4–9, Class VDamped oscillatory magneticfield test100 A/m IEC 61000-4-10, Class VRadiated electromagneticfield disturbance20 V/m, 80-1000 MHz1.4-2.7 GHzIEC 60255-26Radiated electromagneticfield disturbance20 V/m80-1000 MHzIEEE/ANSI C37.90.2Conducted electromagneticfield disturbance10 V, 0.15-80 MHz IEC 60255-26Radiated emission 30-5000 MHz IEC 60255-26Radiated emission 30-5000 MHz IEEE/ANSI C63.4, FCCConducted emission 0.15-30 MHz IEC 60255-26Table 656:InsulationTest Type test values Reference standardDielectric test 2.0 kV AC, 1 min.(SFP galvanic RJ45: 1.0kV, 1 min.)IEC 60255-27ANSI C37.90IEEE 802.3-2015,Environment AImpulse voltage test 5 kV, 1.2/50 ms, 0.5 JInsulation resistance > 100 MW at 500 VDCSection 22 1MRK 505 394-UEN AIED hardware862 Line differential protection RED650 2.2 IECTechnical manual