• Possibilities for blocking and reset• Possibility for manual addition of accumulated time• Reporting of the accumulated time15.11.3 Function block GUID-D0E9688B-C9D9-44B7-BD95-81132CCA5E4F v1TEILGAPCBLOCKINADDTIMERESETALARMWARNINGOVERFLOWACC_HOURACC_DAYIEC15000323.vsdxIEC15000323 V1 EN-USFigure 299: TEILGAPC function block15.11.4 SignalsPID-6998-INPUTSIGNALS v1Table 424:TEILGAPC Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Freeze the accumulation and block the outputsIN BOOLEAN 0 The input signal that is used to measure theelapsed time, when its value is highADDTIME BOOLEAN 0 Add time to the accumulationRESET BOOLEAN 0 Reset accumulated timePID-6998-OUTPUTSIGNALS v1Table 425:TEILGAPC Output signalsName Type DescriptionALARM BOOLEAN Indicator that accumulated time has reachedalarm limitWARNING BOOLEAN Indicator that accumulated time has reachedwarning limitOVERFLOW BOOLEAN Indicator that accumulated time has reachedoverflow limitACC_HOUR REAL Accumulated time in hoursACC_DAY REAL Accumulated time in daysSection 15 1MRK 505 394-UEN AMonitoring604 Line differential protection RED650 2.2 IECTechnical manual