Name Type DescriptionHMICTR4 INTEGER Bitmask output 4 to local remote LHMI inputHMICTR5 INTEGER Bitmask output 5 to local remote LHMI inputHMICTR6 INTEGER Bitmask output 6 to local remote LHMI inputHMICTR7 INTEGER Bitmask output 7 to local remote LHMI inputHMICTR8 INTEGER Bitmask output 8 to local remote LHMI inputHMICTR9 INTEGER Bitmask output 9 to local remote LHMI inputHMICTR10 INTEGER Bitmask output 10 to local remote LHMI inputHMICTR11 INTEGER Bitmask output 11 to local remote LHMI inputHMICTR12 INTEGER Bitmask output 12 to local remote LHMI input12.4.5.3 SettingsPID-3944-SETTINGS v7Table 194:LOCREM Non group settings (basic)Name Values (Range) Unit Step Default DescriptionControlMode Internal LR-switchExternal LR-switch- - Internal LR-switch Control mode for internal/external LR-switchPID-3943-SETTINGS v212.4.5.4 Operation principle M17087-3 v8The function block Local remote (LOCREM) handles the signals coming from thelocal/remote switch. The connections are seen in Figure 169, where the inputs onfunction block LOCREM are connected to binary inputs if an external switch isused. When the local HMI is used, the inputs are not used. The switching betweenexternal and local HMI source is done through the parameter ControlMode. Theoutputs from the LOCREM function block control the output PSTO (PermittedSource To Operate) on Bay control (QCBAY).1MRK 505 394-UEN A Section 12ControlLine differential protection RED650 2.2 IEC 359Technical manual