14.12.4 SignalsPID-6938-INPUTSIGNALS v1Table 320:IB16 Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of functionINP INTEGER 0 Integer InputPID-6938-OUTPUTSIGNALS v1Table 321:IB16 Output signalsName Type DescriptionOUT1 BOOLEAN Output 1OUT2 BOOLEAN Output 2OUT3 BOOLEAN Output 3OUT4 BOOLEAN Output 4OUT5 BOOLEAN Output 5OUT6 BOOLEAN Output 6OUT7 BOOLEAN Output 7OUT8 BOOLEAN Output 8OUT9 BOOLEAN Output 9OUT10 BOOLEAN Output 10OUT11 BOOLEAN Output 11OUT12 BOOLEAN Output 12OUT13 BOOLEAN Output 13OUT14 BOOLEAN Output 14OUT15 BOOLEAN Output 15OUT16 BOOLEAN Output 1614.12.5 Setting parameters ABBD8E242451 v3The function does not have any parameters available in local HMI or Protectionand Control IED Manager (PCM600)14.12.6 Operation principle SEMOD158385-4 v4With integer 15 on the input INP the OUT1 = OUT2 = OUT3= OUT4 =1 and theremaining OUTx = 0 for (5≤x≤16).OUTx represents a value when activated. The value of each of the OUTx is inaccordance with the table IB16_1. When not activated the OUTx has the value 0.Section 14 1MRK 505 394-UEN ALogic480 Line differential protection RED650 2.2 IECTechnical manual