GUID-D6B3DFE3-F7DF-4602-B57E-764DC9EB0D4A v1Table 250:SMPPTRC Output signalsName Type DescriptionTRIP BOOLEAN General trip output signalTRL1 BOOLEAN Trip signal from phase L1TRL2 BOOLEAN Trip signal from phase L2TRL3 BOOLEAN Trip signal from phase L3TR1P BOOLEAN Trip single-poleTR2P BOOLEAN Trip two-poleTR3P BOOLEAN Trip three-poleCLLKOUT BOOLEAN Circuit breaker lockout output (set until reset)START BOOLEAN General start signalSTL1 BOOLEAN Start signal from phase L1STL2 BOOLEAN Start signal from phase L2STL3 BOOLEAN Start signal from phase L3STN BOOLEAN Start signal from neutralFW BOOLEAN General forward signalREV BOOLEAN General reverse signal14.1.5 SettingsGUID-6D6424B9-B676-4D9B-949A-33C74BDC5711 v1Table 251:SMPPTRC Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / OnProgram 3 phase1ph/3ph1ph/2ph/3ph- - 1ph/3ph Three ph; single or three ph; single, twoor three ph triptTripMin 0.000 - 60.000 s 0.001 0.150 Minimum duration of trip output signaltWaitForPHS 0.020 - 0.500 s 0.001 0.050 Secure 3-pole trip when phase selectionfailedTable 252:SMPPTRC Group settings (advanced)Name Values (Range) Unit Step Default DescriptionTripLockout OffOn- - Off Latch TRIP output when SETLKOUTinput is activatedAutoLock OffOn- - Off Activate CLLKOUT output when TRIPoutput is activatedtEvolvingFault 0.000 - 60.000 s 0.001 2.000 Secure 3-pole tripping at evolving faults1MRK 505 394-UEN A Section 14LogicLine differential protection RED650 2.2 IEC 433Technical manual