GUID-47094054-A828-459B-BE6A-D7FA1B317DA7 v6Table 375:VMSQItechnical dataFunction Range or value AccuracyVoltage positive sequence, U1 (10 to 300) V ±0.5% of U at U ≤ 50 V±0.2% of U at U > 50 VVoltage zero sequence, 3U0 (10 to 300) V ±0.5% of U at U ≤ 50 V±0.2% of U at U > 50 VVoltage negative sequence, U2 (10 to 300) V ±0.5% of U at U ≤ 50 V±0.2% of U at U > 50 VPhase angle (10 to 300) V ±0.5 degrees at U ≤ 50 V±0.2 degrees at U > 50 VGUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6Table 376:VNMMXU technical dataFunction Range or value AccuracyVoltage (5 to 175) V ±0.5% of U at U ≤ 50 V±0.2% of U at U > 50 VPhase angle (5 to 175) V ±0.5 degrees at U ≤ 50 V±0.2 degrees at U > 50 V15.2 Gas medium supervision SSIMG GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v315.2.1 IdentificationGUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v4Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberInsulation gas monitoring function SSIMG - 6315.2.2 Functionality GUID-0692CD0D-F33E-4370-AC91-B216CAAAFC28 v6Insulation supervision for gas medium (SSIMG) is used for monitoring the circuitbreaker condition. Binary information based on the gas pressure in the circuitbreaker is used as input signals to the function. In addition, the function generatesalarms based on received information.Section 15 1MRK 505 394-UEN AMonitoring532 Line differential protection RED650 2.2 IECTechnical manual